The WCED brand Type A RCDs detect and respond to sinusoidal residual AC currents
and residual pulsating currents up to 6mA.
Mode: electro-magnetic
Residual current characteristics: A
Rated operational voltage: 230/400V
sensitivity: 30mA Rated conditional short-circuit current: 6kA
Mechanical durability: 4000 cycles
Electrical durability: 2000 cycles
IP degree of protection:
IP20 conforming to BS EN 60529 Ambient temperature: -25 °C – +40 ° C
Complies with BS EN 61008-1
Suitable for EV and solar installations.
| Part code: | Description | Dimensions (WxHxDmm) |
|---|---|---|
| WAR225-030 | 2 pole 25A 30Ma Type A | 36x82x70 |
| WAR240-030 | 2 pole 40A 30Ma Type A | 36x82x70 |
| WAR263-030 | 2 pole 63A 30Ma Type A | 36x82x70 |
| WAR280-030 | 2 pole 80A 30Ma Type A | 36x82x70 |
| WAR2100-030 | 2 pole 100A 30Ma Type A | 36x82x70 |
| WAR425-030 | 4 pole 25A 30Ma Type A | 71.5x82x70 |
| WAR440-030 | 4 pole 40A 30Ma Type A | 71.5x82x70 |
| WAR463-030 | 4 pole 63A 30Ma Type A | 71.5x82x70 |
| WAR480-030 | 4 pole 80A 30Ma Type A | 71.5x82x70 |
| WAR4100-030 | 4 pole 100A 30Ma Type A | 71.5x82x70 |
The WCED brand Time Delayed RCD is used typically when two RCDs are installed in series, and the time delayed RCD enables discrimination, i.e. in the event of a fault only the ‘upstream’ RCD should trip
Residual current characteristics: A
Rated operational voltage: 230/400V
50Hz Earth-leakage sensitivity: 30,100, 300mA
Rated conditional short-circuit current: 6kA
Mechanical durability: 4000 cycles
Electrical durability: 2000 cycles
IP degree of protection: IP20 conforming to:
BS EN 60529 Ambient temperature: -25°C – +40°C
Suitable for EV and solar installations.
Complies with BS EN 61008-1
Recommended Torque: 2.5Nm
| Part code: | Description | Dimensions (WxHxDmm) |
|---|---|---|
| WARTD263-100 | 2 Pole 63Amps 100mA Time Delay | 36x82x70 |
| WARTD280-100 | 2 Pole 80Amps 100mA Time Delay | 36x82x70 |
| WARTD2100-100 | 2 Pole 100Amps 100mA Time Delay | 36x82x70 |
| WARTD463-100 | 4 Pole 63Amps 100mA Time Delay | 71.5x82x70 |
| WARTD480-100 | 4 Pole 80Amps 100mA Time Delay | 71.5x82x70 |
| WARTD4100-100 | 4 Pole 100Amps 100mA Time Delay | 71.5x82x70 |
WCED brand B-Type RCD provide protection against DC residual fault currents, and against AC residual fault currents up to 1000 hertz. They comply with IEC/EN 62423.
Applications included:
E.V & R.V installations, frequency converters, UPS installations, high-frequency Power converters, building site power supply cabins.
Suitable for EV and solar installations.
| Part code: | Description | Dimensions (WxHxDmm) |
|---|---|---|
| WEV240B-030 | 2 pole 40A 30mA Type B | 54x87x79.5 |
| WEV263B-030 | 2 pole 63A 30mA Type B | 54x87x79.5 |
| WEV280B-030 | 2 pole 80A 30mA Type B | 54x87x79.5 |
| WEV2100B-030 | 2 pole 100A 30mA Type B | 54x87x79.5 |
| WEV463B-030 | 4 pole 63A 30mA Type B | 72x87x79.5 |
| WEV4100B-030 | 4 pole 100A 30mA Type B | 72x87x79.5 |
| WEV4100B-100 | 4 pole 100A 100mA Type B | 72x87x79.5 |
The WHP B HP Type RCD is designed to detect and trip under smooth DC faults at any level. Tested to operate at frequencies above 20 kHz, with a minimum tripping threshold of 150 mA for frequencies over 1 kHz.
Type B HP RCDs: Technical Overview
• Two pole two module: Space saving design enables easier installation using standard busbar.
• Compliance with BS 7671 Standards: These devices meet the requirements set out in BS 7671, ensuring they provide the necessary protection in modern electrical installations.
• Effective Operation at High Frequencies: Designed to function reliably at frequencies of 20 kHz and above, making them suitable for applications involving variable-speed drives and heat pump systems.
• Detection of Smooth DC Fault Currents: Capable of detecting and interrupting continuous smooth DC residual currents, which is essential for comprehensive fault protection in systems where such currents may be present.
Type ‘B’ devices are also suitable for type ‘AC’, type ‘A’ and type ‘F’ applications
| Part code: | Description | Dimensions (WxHxDmm) |
|---|---|---|
| WHP240-030 | 2 pole 40A B HP Type RCD | 36x82x70 |
Please fill out the form below for more information
Contact us if you have more questions or wish to place an order.